Introduction
Weishun Electric is devoted to bringing our customers the products with best balanceof price and performance. The HYVZ Series solid dielectric Automatic Circuit Recloser (ACR) represents Houyuan Electric'S promise to endless improving and ongoing developments.
The automatic circuit reclosers are designed for use on overhead distribution lines as well as distribution substation of voltage class up to 38kV.
The tanks are manufactured from stainless steel and powder coated in light grey colour. The product is equipped with a BC300 or BC500 controller. The microprocessor based controller, BC300 or BC500, combines all functions in a single cubicle, including protection, data logging, communication and so on. With built-in communication methods, it is designed as a stand-alone device that can be easily integrated into distribution automation and remote control system.
The product is thoroughly type tested in Houyuan independent laboratory to ensure long life and excellent performance under various environmental conditions.
Overview of Switchgear
● Ganged Operation of Magnetic Actuator The switchgear is operated by a single magnetic actuator ganged with the three vacuum interrupters for both tripping and closing.
● Robust Epoxy Resin Housing The vacuum interrupters are enca psulated with robust hydrophobic epoxy resin housing of unibody casting, featuring thorough insulation to ensure paramount dielectric characteristic.
● Rugged Powder Coated Tank The magnetic actuator and associated mechanism is enclosed in the rugged powder coated tank. The strong base with special surface finishing ensures the capability of working under various environmental conditions.
● The hydrophobic epoxy resin housings are firmly bolted to the lid.
● An external pointer, clearly visible on the base of tank, indicates the“open”or“closed" state of the switchgear. Red for“closed” and Green for“open” ,pulling the yellow ring with hot stick to manually latch the switchgear to “open”
Technical Parameters
Dimensions for Mounting
Description of Controller
Controller
The Microprocessor based controller provides protection, control, monitoring, instrumentation and metering with integrated input and output logic, data logging & fault report.
Communication functionality of the controller is achieved via electrical RS485 port for remote connection. Additional rear ports including RS232 are available for selection.
The Feeder Terminal Unit(FTU) is the core of controller. To prevent any damage to FTU from emergency, the control cubicle contains auxiliary power supply of batteries for uninterruptible power supply, electronic boards and circuit breakers.
A series of protection functions can be set via screen display.
Protection
● Protective Functions
● Phase time overcurrent protection (51P)
● Phase instantaneous overcurrent protection (50P-1)
● Two definite time overcurrent settings (50P-2, 50P-3)
● Ground overcurrent protection (51N)
● Ground instantaneous overcurrent protection (50N-1)
●Two definite time ground overcurrent settings (50N-2, 50N-3)
● Negative sequence overcurrent protection (46)
● Phase and ground directional overcurrent protection ( 67P, 67N;)
● Over-frequency (810, 81V)
● Undervoltage and overvoltage control and alarm (27, 59;)
● Up to four reclose cycles (define a recloser cycle 79-1 79-5; ) close fourtimes / trip five
● Adaptive reclosing shots: each reclose sequence allows independent programming of protective functions Sensitive Earth Fault protection
Current input
Voltage input
Measuring range: 0~ 3V
Power consumption: each phase is not greater than 0.3VA
Overload capacity: 1.4 times the rated value, continuous work
Output
Continuous bearing: 5A
Breaking capacity: DC, inductive load,L / R = 40ms, 220V /0.5A .
Debounce time: 1 ~ 99ms, step 1ms
RS485/RS232
Rate: 1200-38400bps
Default rate: 9600bps
Protocol: Modbus RTU, 1EC60870-5- 101,DNP3.0
Ethernet port (ONLY BC500)
Mode: 10/ 100M (adaptive)
Interface: RJ45
Protocol: Modbus TCP 1 IP,DNP3.0 1EC60870-5 104
Cubicle
The cubicle is integrated with a variety of electronic components, including protection relay and
UPS system for device. Extra components and functions are optional.